Item | Specification | |
1. | Range of tanks and their characteristic features | Vertical cylindrical steel tank for oil and petroleum products (400 m3 to 50 000 m3) |
2. | Internal tank equipment and its configuration | Compatibility is guaranteed by customization according to Data Sheet |
3. | Stored product information
Acid content, pH |
Oil, petroleum products, solvents, aromatic hydrocarbons
pH = 5-9 |
4. | Stored product temperature | -20 0C … + 70o C |
5. | Distance from tank bottom to floating roof on support legs | 1450-1900 mm |
6. | Product pump maximum flow rate | Depends on the number of vacuum breakers. The flow rate of one vacuum breaker is 1500 m3/h |
7. | Pontoon reserve buoyance at minimum product density | Not less than 100 % of the pontoon weight |
8. | Pontoon efficiency | Depends on the actual operating conditions. In afloat position and at a temperature above 00 C the emissions reduction efficiency factor amounts to 98-99,5 % |
9. | Product vapour content in the pontoon space at “afloat” position | Less than 50 % of hydrocarbons’ saturated vapour |
10. | Warranty period | 3 years |
11. | Anti-static system | Every conductive part of the pontoon equipment is electrically interconnected by at least two flexible stainless steel cables with the outer construction |
12. | Compliance with normative documents of The Federal Environmental, Industrial and Nuclear Supervision Service of Russia (Rostekhnadzor) | Design, fabrication and inspection of FAIFR-1 correspond to the requirements of normative documents of The Federal Environmental, Industrial and Nuclear Supervision Service of Russia, which is confirmed by approval of «Technical conditions» on the FAIFR-1 and issue of the permit for production and application of the pontoon-type internal floating roof FAIFR-1 |